70 RT-SVP04F-EN
System Programming SETUP
Ventilation Override Definition Mode A Used With: All units with VOM
installed with Return Fan.
Possible Values: Return Fan/
Exhaust Damper: OFF/CLOSED, ON/
OPEN
Return Fan/Exhaust Dampers OFF/CLOSED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Ventilation Override Definition Mode A Used With: All Units when VOM and
Power Exhaust without Statitrac is
installed
Factory Presets: Refer to
Definitions
Possible Values: ON, OFF
Exhaust Fan ON
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Ventilation Override Definition Mode A Used With: All units with VOM
installed and Return Fan with
Statitrac installed.
Possible Values: Return Fan VFD
Command: MIN, MAX
Return Fan VFD Command Min
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Ventilation Override Definition Mode A Used With: All Units when VOM and
an economizer is installed
Factory Presets: Refer to
Definitions
Possible Values: OPEN/CLOSED
Outside Air Dampers OPEN
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Ventilation Override Definition Mode A Used With: All Units
Factory Presets: Refer to
Definitions
Possible Values: ENERGIZED/
DEENERGIZED
VAV Box Relay DEENERGIZED
1.Press the NEXT key until the following screen is displayed.
Ventilation Override Definition Mode A Used With: All Units when VOM and
Gas, Electronic or Hydronic Heat is
installed
Factory Presets: Refer to
Definitions
Possible Values: OFF, IN CONTROL
Heat OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.