RT-SVP04F-EN 47
System Operating Status
Temp Measured By Sensor Connected To
RTM SUPPLY AIR TEMP INPUT 50.0 F
Used With: All Units—EER = No
sensor connected or sensor failure
1. Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
RTM ZONE TEMP INPUT 82.0 F
Used With: All Units—EER = No
sensor connected or sensor failure
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
NSB Panel Temp Sensor Input 79.5 F
Used With: All Units when Night
Setback (NSB) is installed
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
RTM AUX TEMP INPUT 62.0 F
Used With: All Units—EER = No
sensor connected or sensor failure
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
RTM OUTSIDE AIR TEMP INPUT 86.0 F
Used With: All Units—EER = No
sensor connected or sensor failure
1. Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
HEAT MODULE AUX TEMP INPUT 82.0 F
Used With: All Units when Gas,
Electric, Hydronic or Modulating
Heat is installed—EER = No sensor
connected or sensor failure
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
ECEM RETURN AIR TEMP INPUT 78.0 F
Used With: All Units when
Comparative Enthalpy is installed—
EER = No sensor connected or
sensor failure
1. Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
VCM MODULE AUX TEMP INPUT 50.0 F
Used With: All Units when VCM is
installed and OA Preheater is
enabled—EER = No sensor
connected or sensor failure
1. Press the NEXT key until the following screen is displayed.
Compressor Module Ckt 1
Evap Temp 49.4 F Sat Cond Temp 95.0 F
Used With: All Rooftop Units and
Air Handlers when DX cooling is
installed
1. Press the NEXT key until the following screen is displayed. (if applicable)
Compressor Module Ckt 2
Evap Temp 50.6 F Sat Cond Temp 97.0 F
Used With: All Rooftop Units and
Air Handlers when DX cooling is
installed
1. Press the NEXT key until the following screen is displayed.