Start-Up and Shutdown
RTAF-SVX001K-EN 65
Running (Lag Compr/Circuit Start - Run)
The figure below shows a typical start and run sequence
for the lag compressor and its circuit.
Figure 43. Sequence of operation: running (lag compressor/circuit start nd run)
*Note:Thedecisiontostageonoroffanothercompressorisdeterminedby
the Average Running Compressor Load Command,Water Temperature Error,and Time Since Last Stage
All
Compressors
Running
Chiller and Both Circuit
Modes are “Running”
Modulate
Compressorfor
Capacity Control
De-energize
Oil Heaters
Of Lag Circuit
Control Both Circuit
Condenser Fans for
OptimumDifferential
Pressure,
ƒ(Cprsr Spd,OA Temp)
Enforce All Running ModeDiagnostics for Chiller,Lead Compressor and its Circuit
Modulate
Compressor
for Limit
Control
Modulate Compressor
for
Capacity Control
0
M
Exit
LimitMode
Enter
LimitMode
Running
EnergizeMaximum
Capacity Relay after the
Adjustable Filter Time
(0 to 1500 Seconds)
Continue
Running
(All
Cprsrs &
Max
Capacity
Maximum Capacity
Submode
Running
Lag Circuit:
Running Limit
All Compressors Running
At or Near Max Capacity
(Unable to Achieve CWSP)
Modulate EXV for
Pressure Control