Start-Up and Shutdown
68 RTAF-SVX001K-EN
Normal Shutdown to Stopped or Run Inhibit
The figure below shows the Transition from Running
through a Normal (friendly) Shutdown. The Dashed lines
on the top attempt to show the final mode if you enter the
stop via various inputs.
Figure 46. Sequence of events: normal shutdown to stopped or run inhibit
*Operational Pumpdown is required if the Outdoor Air
Temperature is less than 50F,or the Entering Evaporator Water
Temperature is greater than (outdoor air temperature 10°F). With
AFD,compressors will beatmaxspeed for operational
pumpdown.
**Operational Pumpdown: See Satisfied Setpoint Operational
Pumpdown sequencediagramforspecific criteria
***Automatic evaporator isolation valve control will close valve if
Outdoor Ambient Air Temperature at circuit shutdown is less than
evaporator leaving water cutout setpoint plus C.
Themaximumallowed time for Operational Pumpdown is:Max
pumpdown time =setting x number of compressors configured on
the circuit.
Note:If Free Cooling is active,thelast stageof cooling to turn off
will be Free Cooling.
/
/
/
6
1
/
/
2
/
/
/
2
2
/
/
0
1
2
-
8
/
/
/
8
1
/
/
5
/
/
/
5
2
/
/
0
1
2
Shutting Down
Running Circuit Modes:Shutting Down
SubMode:Operational Pumpdown
*
8
/
8
8
1
5
/
5
5
2
0
1
2
1
2
/
2
2
1
1
/
1
2
0
1
2
6
/
66
1
3
/
33
2
0
1
2
Operational Pumpdown
(See max allowed time below)
Fully Close EXV
PerformOperational
PumpdownforAll
Running Circuits if
Required
*
IF *
Close EXV
(0to 25Seconds)
2
2
0
0
1
2
6
/
66
1
2
/
22
2
0
1
2
-
1
2
/
22
1
1
/
1
2
0
1
2
Check for
Normal Pumpdown
Termination Criteria Met
**
6
/
/
66
1
1
1
1
1
/
/
5
5
5
5
/
/
5
2
2
2
2
2
2
/
/
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
2
2
2
2
2
2
2
No Pumpdown Required
Pumpdown
Required
EvaporatorPump Off Delay
(Adjustable 1 to 30 Minutes)
Send Stop Command to
All
Running Compressors
EnergizeAll Heaters
Fully Close Both EXVs
Turn Off All Running
Circuits Condenser Fans
De-Energize Evaporator
Water Pump Relay
Stopped
or
Run Inhibi
One or
More
Circuits
Running
Normal Pumpdown Termination**
Criteria is Metfor All Circuits
Local Stop
Chiller Level Diagnostic Normal Shutdown Latched
Chiller Level Diagnostic Normal Shutdown Nonlatched
Building Automation SystemStop
External Auto-Stop
8
r
r
i
i
/
aa
8
a
a
1
a
a
/
/
a
a
5
i
i
s
s
/
s
s
5
s
s
2
s
s
/
/
s
s
0
M
M
1
M
M
2
e
e
-
t
t
1
f
f
o
o
0
o
o
/
r
r
0
1
r
r
A
A
//
r
r
A
A
/
AA
ll
A
A
2
l
l
/
/
ll
ll
0
C
C
C
C
2
i
i
r
r
Shutting Down
CircuitModes:
Auto
1
0
/
0
1
/
/
6
/
66
2
/
/
0
1
2
-
1
2
/
2
1
/
/
1
/
2
/
/
0
1
2
Stopped or Run Inhibit
CircuitModes:
Stopped or Auto
1
0
/
00
1
7
/
77
2
0
1
2
Automatic Evaporator
Isolation Valve control
mayclose valve
EconomizerEEV and
port loader close