Figure 44. Sequence of events: satisfied setpoint
*Operational Pumpdown is required if the Outdoor Air Temperature is less than 50F,or the Entering
Evaporator Water Temperature is greater than (outdoor air temperature – 10°F). With AFD, compressors
will be atmax speed for operational pumpdown.
** Operational pumpdown is terminated normallyin the following configurations when:
Water with 2-Pass Evaporator:
-The evaporator (suction)pressure is at or below the “Pumpdown Termination Pressure” setting OR
LERTC saturated pressure (28.6F), which ever is greater
-The condenser (compressordischarge)pressureexceeds 315psia.
-The compressorpressure ratio exceeds 8.
-The system differential pressure exceeds 265psid or <25min.
Glycol with 2-Pass Evaporator:
Theevaporator (suction)pressure is at or below the “Pumpdown Termination Pressure” setting OR
LERTC saturated pressure (per guidance -5F minimum), which ever is greater
-The condenser (compressordischarge)pressureexceeds 315psia.
-The compressorpressure ratio exceeds 8.
-The system differential pressure exceeds 265psid or <25min.
Water with SinglePass Evaporator:
-The evaporator (suction)pressure is at or below the “Pumpdown Termination Pressure” setting OR
LERTC saturated pressure (32F), which ever is greater
-The condenser (compressordischarge)pressureexceeds 315psia.
-The compressorpressure ratio exceeds 12.3
-The system differential pressure exceeds 265psid.
Glycol with Single Pass Evaporator:
-The evaporator (suction)pressure is at or below the “Pumpdown Termination Pressure” setting OR
LERTC saturated pressure (per guidance -5F minimum), which ever is greater
-The condenser (compressordischarge)pressureexceeds 315psia.
-The compressorpressure ratio exceeds 12.3
-The system differential pressure exceeds 265psid.
Themaximumallowed time forOperational Pumpdown is Max Pumpdown Timesetting (default to 120
sec.)*number of compressors configured on the circuit.
***Automatic evaporator isolation valve control will close valve if Outdoor Ambient Air Temperature at
circuit shutdown is less than evaporator leaving water cutout setpoint plus 3°C.
****If Condenser Refrigerant Tanks are installed