10
BAS-SVX090B-EN
General Information
Specifications
Storage
Temperature -67°F to 203°F (-55°C to 95°C)
Relative humidity Between 5% to 95% (non condensing)
Operating
Temperature -40°F to 158°F (-40°C to 70°C)
Humidity Between 5% to 95% (nonconducting)
Power
20.4–27.6 Vac (24 Vac, ±15% nominal) 50–60 Hz 24 VA
Mounting weight of controller Mounting surface must support 0.80 lb. (0.364 kg)
Environmental rating (enclosure)
NEMA 1
Plenum rating
Not plenum rated. The Symbio 500 must be mounted within a rated enclosure when installed in a
plenum.
Wiring/Transformer
16 AWG (recommended) copper wire
• UL Listed, Class 2 power transformer 20.4–27.6 Vac (24 Vac, ±15% nominal)
• The transformer must be sized to provide adequate power to the controller and outputs. For more information on transformer sizing, see BAS-SVX090*-EN.
Agency Compliance
• UL60730-1 PAZX (Open Energy Management Equipment
• UL94-5V Flammability
• CE Marked. The European Union (EU) Declaration of Conformity is available from your local Trane® office.
• UKCA Marked
• FCC Part 15, Subpart B, Class B Limit
• VCCI-CISPR 32:2016: Class B Limit
• AS/NZS CISPR 32:2015: Class B Limit
• CAN ICES-003(B)/NMB-003(B)
• The Symbio 500 is BTL certified as a B-BC profile device. A complete list of Trane certified devices is available at www.bacnetinternational.org.
Note: The Symbio 500 programmable controller supports being a BBMB. This is a specific functionality and is different than the profile certification. The
Symbio 500 cannot be a router.
Sensors
WARNING
Electrical Shock Hazard!
Failure to follow instructions below could result in death or serious injury.
Do not mix Class 1 and Class 2 voltage wiring in an enclosure or on a controller without an
approved barrier between wiring.
The Symbio 500 controller supports the following sensor types:
• Zone temperature sensors (resistive and thermistor)
• Linear 0–20 mA, such as humidity sensors
• Linear 0–10 Vdc, such as indoor air-quality sensors
• 3-wire pressure transducer inputs
• RTD sensors