34
BAS-SVX090B-EN
Figure 14. Analog outputs
1. Connect the shield to a common terminal at the terminal board and tape it back at the input device.
Note: Do not use the shield as the common connection. For 2-wire applications, use a 2-conductor
cable with separate shield.
2. Connect the signal wire to an available output terminal.
3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required.
4. Use the Tracer TU service tool to configure the input for analog operation.
Relay (Dry Contact/Binary Outputs)
The Symbio 500 has three relay binary outputs used as powered outputs. All outputs are isolated from
one another and from the ground and power. The illustration below shows a typical wiring for relays,
binary outputs.
Wiring