BAS-SVX090B-EN
31
Figure 11. 0–10 Vdc analog inputs
To wire a 0–10 Vdc analog input:
1. Connect the shield wire (as common connection) to a common terminal.
2. Connect the signal wire to an available input terminal.
3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required.
4. Use the Tracer TU service tool to configure the universal input for analog operation.
0–20 mA Analog Inputs
The universal inputs can be used to receive a 0–20 mA analog signal from sensors such as humidity
sensors and pressure sensors. The illustration below shows a typical wiring for analog inputs, 0–20 Vdc.
Wiring