24
BAS-SVX090B-EN
Basic Checks
For devices with input/output types listed below, verify their basic functionality:
• Binary inputs: check that they are opening and closing. Also check for 24 Vac if they provide their
own power. With a Trane-provided 24 Vac, check to make sure it is dry contact and working.
• Thermistors: check for 10K using a digital multimeter (DMM).
• Thumb wheels: verify mechanical operation.
• Binary outputs: check for any dead shorts.
• Analog outputs: check that no A/C voltage is present and that the load has no 24 Vac across it or
120 Vac.