48
BAS-SVX090B-EN
General Information Checkout Procedure Measurement
Expected Value
Method 2 interferes less in
regards to the system. In
voltage mode, the DMM
affects the circuit less.
Additional information is
needed to translate the
voltage measured to current
flowing through the circuit.
Step 1
Measure AC voltage across
the voltage input
Vac ≈ 0.0 V
AC voltage will affect further
measurement
Step 2
Measure DC voltage across
the voltage termination
See the chart below
2.5
3
3.5
4
4.5
1.5
0
0.5
1
2
Measured Voltage Across a Linear Current Input
Linear Current Input–mA
10 124 60 2 16 188 2014
Voltage Measured Across Input–Vdc
Commissioning and Troubleshooting in Powered State