Inspect for Description
Input power wiring Check for:
Loose connections.
Proper fusing.
Blown fuses.
Memory module
Check that the memory module is plugged in correctly.
Motor
Check nameplate ratings of the motor.
Ensure that motor ratings coincide with frequency converters.
Ensure that the frequency converter motor parameters (parameter 1-20 Motor Power to
parameter 1-25 Motor Nominal Speed) are set according to motor ratings.
Output to motor wiring Check for:
Loose connections.
Switching components in output circuit.
Faulty contacts in switch gear.
PROFIBUS option
Check that the option is mounted correctly on the control card.
Programming Ensure that frequency converter parameter settings are correct according to:
Motor.
Application.
I/O conguration.
Proper clearance The frequency converter requires top and bottom clearance adequate to ensure proper air ow for
cooling in accordance with the frequency converter size. When the heat sink is exposed at the rear of
the frequency converter, mount the frequency converter on a
at,
solid surface.
Vibration
Check for exposure to an unusual amount of vibration.
When the frequency converter experiences a high level of vibration, ensure solid mounting or use
shock mounts.
Table 4.1 Visual Inspection Check List
Troubleshooting TR150 and TR170 Service Manual