Appendix
108 CNT-SVX05B-EN
Table 77. Hard-wired CO
2
sensor values
Current (mA)
CO
2
(ppm)
Current (mA)
CO
2
(ppm)
40 40
5 125 5.6 200
6250 7.2400
7375 8.8600
8500 10.4800
9 625 12 1000
10 750 13.6 1200
11 875 15.2 1400
12 1000 16.8 1600
13 1125 18.4 1800
14 1250 20 2000
15 1375
16 1500
17 1625
18 1750
19 1875
20 2000