Chapter 5 Configuration
74 CNT-SVX05B-EN
Table 30. Controller location label configuration
Location label Maximum length
Name the controller to identify its
physical location.
30 characters
Table 31. Heating configuration
Heating type Heating source
Electric heat
stages
Face-and-bypass
damper
•Preheat
•Reheat
Hydronic N/A • None
• Face-and-
bypass damper
Steam N/A N/A
Staged electric
heat
1
1, 2, 3, or 4 N/A
Electric heat
sequencer
2
1, 2, 3, 4, 5, or 6 N/A
1 When heating source is staged electric heat, the controller binary outputs BO6, BO5,
BO4, and BO3, are used to control discrete electric heat stages 1, 2, 3, or 4, respec-
tively.
2 When heating source is electric heat sequencer the heat analog output AO3 is used
to control a step controller/sequencer, up to six stages.
Table 32. Supply fan heat source configuration
Heating source
Draw-through
Blow-through
Note: Configure the supply fan to indicate the relationship of the supply fan to the heating
source. For example, if the heating source is located after the supply fan in the air stream,
blow-through should be selected. If the unit is heating and cooling (two-pipe changeover),
indicate the relationship of the supply fan to the secondary heat source, if installed.
Table 33. Cooling source configuration
Cooling source DX cooling stages Outdoor air damper
Hydronic
1
N/A • None
• Outdoor air damper
DX cooling
2
1, 2, 3, or 4
1 When cooling source is hydronic, the cool analog output AO2 is used to control a
modulating valve.
2 When cooling source is DX cooling, controller binary outputs BO3, BO4, BO5, and
BO6 are used to control discrete compressor stages.