Configuration
CNT-SVX05B-EN 75
Table 34. Binary output configuration
Terminal label
Function
1
BO1 Supply fan
BO2 Exhaust fan
BO3 None
DX cooling stage 1
Electric heat stage 4
BO4 None
DX cooling stage 2
Electric heat stage 3
BO5 None
DX cooling stage 3
Electric heat stage 2
BO6 None
DX cooling stage 4
Electric heat stage 1
1 Factory-installed Tracer AH540 controllers are configured according to model num-
ber specification.
Table 35. Analog output configuration
Analog
output
1
Function
Output voltage
range
Valid range
2
Default value
AO1 Supply fan speed 0–10 Vdc
•210 Vdc
•Normally slow
•Normally fast
•010 Vdc
Normally open
AO2 Cool output 0–10 Vdc
•210 Vdc
Normally open
Normally closed
•210 Vdc
Normally closed
AO3 Heat output 0–10 Vdc
•210 Vdc
Normally open
Normally closed
•210 Vdc
Normally open
AO4 Face-and-bypass damper 0–10 Vdc
•210 Vdc
•Normally face
Normally bypass
3
•210 Vdc
•Normally face
AO5 Outdoor air damper 0–10 Vdc
•210 Vdc
Normally open
Normally closed
•210 Vdc
Normally closed
1 The Rover service tool uses the unit type to determine and download the proper default analog output configuration. For
example, if you configure the controller as a space temperature controller, Rover will not allow AO1 to be configured for a sup-
ply fan speed output. Analog output AO1 is only used when the controller is configured as a variable-air-volume controller.
2 The normally open/closed configuration item refers to the inactive state of the end device, such as a cooling valve. If the device
is a normally open valve, the configuration for analog output AO2 must be normally open.
3 A normally face damper is positioned full coil face, and a normally bypass damper is positioned full coil bypass when the ana-
log output is at 0 Vdc.