Chapter 5 Configuration
76 CNT-SVX05B-EN
Table 36. Analog input configuration
Analog input
1
Function Calibration range Default value
IN1 Space temperature ±10.0°F (±5.7°C)
(0.1°F resolution)
0°F
IN2 Setpoint ±10.0°F (±5.7°C)
(0.1°F resolution)
0°F
IN3 Fan switch N/A N/A
IN4 Discharge air temperature N/A N/A
IN5 Outdoor air temperature N/A N/A
IN6 Mixed-air temperature N/A N/A
Duct static Duct static pressure N/A N/A
IN13 • Space relative humidity
•CO2 sensor
• Entering water temperature
• Evaporator refrigerant temperature
• Generic temperature
N/A Space relative humidity
1 The Rover service tool uses the unit type to determine and download the proper default analog input configuration.
Table 37. Binary input configuration
Binary input
1
Function Valid range Default Configuration
IN7 • Low temp detect
• Coil defrost
• Not used
• Normally open
• Normally closed
Dependent on air-handling unit type
IN8
• Run/stop
• Not used
• Normally open
• Normally closed
• Latching or nonlatching
• Run/stop
• Normally open
• Latching diagnostic
2
IN9 • Occupancy
•generic
• Not used
• Normally open
• Normally closed
• Occupancy
• Normally open
IN10 • Supply fan status
• Not used
• Normally open
3
• Normally closed
3
Sales order dependent
IN11 • Filter status
• Not used
• Normally open
4
• Normally closed
4
Sales order dependent
IN12 • Exhaust fan status
• Coil defrost
• Not used
• Normally open
• Normally closed
Sales order dependent
1 The Rover service tool uses the unit type to determine and download the proper default binary input configuration.
2 The run/stop binary input can be configured as a latching or nonlatching diagnostic.
3 When the supply fan is Off, the state of the fan status device is its normal state. For example, if the fan status switch (end
device) is normally open when the fan is Off, the controller should be configured for a normally open fan status input.
4 When the supply fan is Off, the state of the filter status device is its normal state. For example, if the filter status switch (end
device) is normally closed when the fan is Off, the controller should be configured for a normally closed filter status input.