DynaView Interface
RLC-SVU05A-E420
Report name: System Condenser
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Cond Entering Water Temp + XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
2. Cond Leaving Water Temp + XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
3. Cond Water Flow Switch Status (Flow, No Flow) Enum Water Cooled only (i.e. RTWD or RTUD with ACFC=None))
4. Outdoor Air Temperature + XXX.X Temperature Only if OA sensor is installed
5. Cond Head Pressure Ctrl Command XXX % Only if Cond Head pressure control option is installed
Report name: Circuit Condenser
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Cond Entering Water Temp + XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
2. Cond Leaving Water Temp + XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
3. Condenser Air Flow XXX % Air Cooled (i.e RTUD with ACFC=INT)
4. Cond Inverter Speed XXX %
5. Outdoor Air Temperature + XXX.X Temperature Only if OA sensor is installed
6. Cond Water Flow Switch Status (Flow, No Flow) Enum Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
7. Cond Sat Rfgt Temp + XXX.X Temperature
8. Cond Rfgt Pressure XXX.X Pressure
9. Differential Pressure XXX.X Pressure
10. Cond Approach Temp + XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Report name: System Compressor
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Average Line Current XXX %RLA
2. Unit Volts XXX Volts
3. Unit Running Time XXXX:XX hr:min
4. Power Demand kW Only if pwr meter option installed
5. Power Demand Time Period min Only if pwr meter option installed
6. Energy Consump-Resettable kWh Only if pwr meter option installed
7. Time of Last Reset time-date Only if pwr meter option installed
8. Energy Consump-NonReset Kwh Only if pwr meter option installed
Air Cooled with Low Ambient Var Spd fan (i.e RTUD with ACFC<>None and
with LAFC = VARA or VARP)