DynaView Interface
21RLC-SVU05A-E4
Report name: Circuit Compressor
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Oil Pressure XXX.X Pressure
2. Compressor Rfgt Dschg Temp + XXX.X Temperature
3. Cond Sat Rfgt Temp + XXX.X Temperature
4. Average Line Current XXX %RLA
5. % RLA L1 L2 L3 XXX.X %RLA
6. Amps L1 L2 L3 XXX.X Amps
7. Phase Voltages XXX Vac Only if pwr meter option installed
8. Power Consumption XXX kW Only if pwr meter option installed
9. Load Power Factor X.XXX Only if pwr meter option installed
10. Compressor Starts: XXXX Integer
11. Compressor Running Time: XXXX:XX hr:min
Report name: System ASHRAE Chiller Log
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Current Time/Date XX:XX mmm dd, yyyy Time / Date
2. Chiller Mode Enum
3. Active Chilled Water Setpoint XXX.X Temperature
4. Active Hot Water Setpoint XXX.X Temperature Hot Water Option installed only
5. Evap Entering Water Temperature XXX.X Temperature
6. Evap Leaving Water Temperature XXX.X Temperature
7. Average Leaving Water Temp XXX.X Temperature
8. Evap Water Flow Switch Status Enum
9. Outdoor Air Temperature XXX.X Temperature Only if OA sensor is installed
Report name: Circuit ASHRAE Chiller Log
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution Units Dependencies
1. Circuit Mode Enum
2. Evap Sat Rfgt Temp XXX.X Temperature
3. Suction Pressure XXX.X Pressure
4. Evap Approach Temp XXX.X Temperature
5. Cond Sat Rfgt Temp XXX.X Temperature
6. Cond Rfgt Pressure XXX.X Pressure
7. Cond Approach Temp XXX.X Temperature Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
8. Compressor Starts XXXX Integer
9. Compressor Running Time XX:XX Hours:Minute
Items 1 - 9 will be unique for each circuit, ckt1, and ckt2.