DynaView Interface
23RLC-SVU05A-E4
Chiller
Description Units
1. Front Panel Cool/Heat Command (Cool, Heat), Cool Enum
2. Front Panel Chilled Water Setpt Temperature
3. Front Panel Hot Water Setpt Temperature
4. Front Panel Current Limit Setpt 1 %RLA
5. Front Panel Ice Build Cmd On/Auto Enum
6. Front Panel Ice Termination Setpoint XXX.X Temperature
7. Setpoint Source Enum
8. Leaving Water Temp Cutout XX.X Temperature
9. Low Refrigerant Temp Cutout XX.X Temperature
10. Staging Sequence (Bal Starts/Hrs, Fixed), Bal Starts/Hrs Enum
11. Condenser Pump Prestart Time XX , 0 minutes
Feature Settings
Note: Purple Box Designates Phase 2 Air Cooled RTUD items.
Description Units
1. Cooling Low Ambient Lockout (Enable, Disable), Enable Enum
1a. Cooling Low Ambient Lockout (Enable, Disable), Enable Enum
1b. Cooling Low Amb Lockout Setpt XXX.X Temperature
2. Noise Setback Command (Auto, On, Schedule), Auto Enum
3. Ice Building (Enable, Disable), Disable Enum
4. Ext Chilled/Hot Water Setpt (Enable, Disable), Disable Enum
5. Ext Current Limit Setpoint (Enable, Disable), Disable Enum
6 Chilled Water Reset
6a. Chilled Water Reset Enum
6b. Return Reset Ratio XXX Percent
6c. Return Start Reset XXX.X Temperature
6d. Return Maximum Reset XXX.X Temperature
6e. Outdoor Reset Ratio XXX Percent
6f. Outdoor Start Reset XXX.X Temperature
6g. Outdoor Maximum Reset XXX.X Temperature
7. LCI-C Diag Language Enum
8. LCI-C Diag Encoding (Text, Code) Text Enum
Items 1 and 6 are top level. If user presses this line another screen opens to allow user to change relevant
setpoints.
Items 7 and 8 are present if comm5 LCI-C option is installed.
Resolution or (Enumerations),
Default
Resolution or (Enumerations),
Default
(BAS/Ext/FP, Ext/ Front Panel,
Front Panel), BAS/Ext/FP
(2)
+ XXX.X
(2)
+ XXX.X
(Const Return, Outdoor,
Return, Disable), Disable
(Const Return, Outdoor,
Return, Disable), Disable
(English, Selection 2,
Selection 3) English (0)