DynaView Interface
RLC-SVU05A-E424
System Manual Control Settings
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description Resolution or (Enumerations), Default Units Monitor Value Dependency
1. Evap Water Pump (Auto, On), Auto (6)
Enum
1) Water Flow status
1.a.Evap Water Pump <Auto / On Buttons> 2) Override Time Remaining
2. Cond Water Pump (Auto, On), Auto (6)
Enum
1) Water Flow status
Water Cooled only (i.e.
RTWD or RTUD with
ACFC=None)
2.a. Cond Water Pump <Auto / On Buttons> 2) Override Time Remaining
3. Head Pressure Control (Auto, Manual), Auto (7)
Enum
1) Override status -
Auto/Manual
Only if Cond Head pressure
control option is installed
3.a. Head Pressure Control <Auto / Manual Buttons> (7)
4. Staging/Stepping Control (Auto, Manual), Auto (7)
Enum
Only if Cond Head pressure
control option is installed
4.a. Staging/Stepping Control <Auto / Manual Buttons> (7)
5. Capacity Modulation Control (Auto, Manual), Auto (7)
Enum
Only if Cond Head pressure
control option is installed
5a. Capacity Modulation Control <Auto / Manual Buttons> (7)
6. Clear Energy Consumption
1) Resettable Energy consumption
totalization (kWh)
Enum
1) Resettable Energy
consumption totalization (kWh)
Only if Energy Meter option
is installed
6.a. Clear Energy Consumption <Clear Button>
Circuit Manual Control Settings
Description Resolution or (Enumerations), Default Units Monitor Value
1. Compressor Pumpdown (Continue, Not Available)
Enum
1) Override status:
NotAvailable / Continue / Starting / Pumpdown
1.a. Compressor Pumpdown <Pumpdown / Abort Buttons> (8) 2) Suction Pressure
2. Front Panel Ckt Lockout (Not Locked Out, Locked Out), Not Locked Out
Enum
2.a. Front Panel Ckt Lockout <Not Locked Out / Locked Out Buttons>
3. Expansion Valve Control (Auto, Manual)
Enum
3.a. Expansion Valve Control <Auto / Manual Buttons> (7)