43CG-SVU02C-E4
Main Processor Diagnostics
Diagnostic Name
Affects
Ta r g e t
Severity Persistence
Active Modes
[Inactive Modes]
Criteria Reset Level
Starter Module
Memory Error Type
1 - Starter 2A
None Info
Latch
All Checksum on RAM copy of the Starter LLID
configuration failed. Configuration recalled from
EEPROM.
Local
Starter Module
Memory Error Type
2 - Starter 1A
Circuit Immediate Latch All
Checksum on EEPROM copy of the Starter LLID
configuration failed. Factory default values used.
Local
Starter Module
Memory Error Type
2 - Starter 2A
Circuit Immediate Latch All
Checksum on EEPROM copy of the Starter LLID
configuration failed. Factory default values used.
Local
Pumpdown
Terminated -
Circuit 1
Circuit Info NonLatch
Service or
Operational
Pumpdown
Operational or Service Pumpdown cycle for this circuit
was terminated abnormally due to excessive time (op
pd only) or due to a specific set of diagnostic criteria -
but w/o associated latching diagnostics . (RTWD max
Operation Pumpdown = 2 min)
Local
Pumpdown
Terminated -
Circuit 2
Circuit Info NonLatch
Service or
Operational
Pumpdown
Operational or Service Pumpdown cycle for this circuit
was terminated abnormally due to excessive time (op
pd only) or due to a specific set of diagnostic criteria -
but w/o associated latching diagnostics . (RTWD max
Operation Pumpdown = 2 min)
Local
Pumpdown
Terminated by
Time - Circuit 1
Circuit Info NonLatch Service Pumpdown
Service Pumpdown cycle for this circuit was
terminated abnormally due to excessive time (RTWD
max Service Pumpdown = 4 min).
Local
Pumpdown
Terminated by
Time - Circuit 2
Circuit Info NonLatch Service Pumpdown
Service Pumpdown cycle for this circuit was
terminated abnormally due to excessive time (RTWD
max Service Pumpdown = 4 min).
Local
MP: Invalid
Configuration
None Immediate Latch All
MP has an invalid configuration based on the current
software installed.
Remote
MP Application
Memory CRC Error
Chiller Immediate Latch All Modes Memory error criteria TBD Remote
MP: Non-Volatile
Memory Reformat
None Info Latch All
MP has determined there was an error in a sector of
the Non-Volatile memory and it was reformatted.
Check settings.
Remote
Check Clock
Chiller Info Latch All
The real time clock had detected loss of its oscillator
at some time in the past. Check / replace battery?
This diagnostic can be effectively cleared only by
writing a new value to the chiller's time clock using
the TechView or DynaView's "set chiller time"
functions.
Remote
MP: Could not
Store Starts and
Hours
None Info Latch All
MP has determined there was an error with the
previous power down store. Starts and Hours may
have been lost for the last 24 hours.
Remote
MP: Non-Volatile
Block Test Error
None Info Latch All
MP has determined there was an error with a block in
the Non-Volatile memory. Check settings.
Remote
Starter Failed to
Arm/Start -
Cprsr 1A
Circuit Normal
Latch
All Starter failed to arm or start within the allotted time
(15 seconds).
Local
Starter Failed to
Arm/Start -
Cprsr 2A
Circuit Normal
Latch
All Starter failed to arm or start within the allotted time
(15 seconds).
Local
Oil Analysis
Recommended -
Ckt #1
Circuit Info
Latch
"Service Messages"
enabled
Diagnostic occurs when accumulated circuit operating
hours since last initialized exceeds 2000 hours.
Diagnostic can be manually cleared but will reoccur
every month (720 hours on real time clock) as long as
accumulator is not re-initialized.
Remote