Trane Tracer CH530 - Oil Analysis, Filter Change, and Software Diagnostics

Trane Tracer CH530
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CG-SVU02C-E444
Main Processor Diagnostics
Diagnostic Name
Affects
Ta r g e t
Severity Persistence
Active Modes
[Inactive Modes]
Criteria Reset Level
Oil Analysis
Recommended -
Ckt #2
Circuit Info
Latch
"Service
Messages" enabled
Diagnostic occurs when accumulated circuit operating
hours since last initialized exceeds 2000 hours.
Diagnostic can be manually cleared but will reoccur
every month (720 hours on real time clock) as long as
accumulator is not re-initialized.
Remote
Oil Filter Change
Recommended -
Cprsr 1A
Circuit Info
Latch
"Service
Messages" enabled
(After RTUD release in Fall of 09:) Diagnostic occurs only
when "service messages" are enabled and when Oil
Filter Life remaining falls below 5 %. Diagnostic can be
manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life
remaining does not rise above 20% (through normal
calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service
messages" are enabled and when average oil pressure
drop exceeds 18%. Diagnostic can be manually cleared
but will reoccur every month (720 hours on real time
clock) as long as average pressure drop does not fall
below 16%.
Remote
Oil Filter Change
Recommended -
Cprsr 2A
Circuit Info
Latch
"Service
Messages" enabled
(After RTUD release in Fall of 09:) Diagnostic occurs only
when "service messages" are enabled and when Oil
Filter Life remaining falls below 5 %. Diagnostic can be
manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life
remaining does not rise above 20% (through normal
calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service
messages" are enabled and when average oil pressure
drop exceeds 18%. Diagnostic can be manually cleared
but will reoccur every month (720 hours on real time
clock) as long as average pressure drop does not fall
below 16%.
Remote
LCI-C Software
Mismatch: Use BAS
Tool
Chiller Info
NonLatch
All The neuron software in the LCI-C module does not
match the chiller type. Download the proper software
into the LCI-C neuron. To do this, use the Rover service
tool, or a LonTalk® tool capable of downloading
software to a Neuron 3150®.
Remote
Software Error
1001: Call Trane
Service
All
functions
Immediate Latch
All
A high level software watchdog has detected a
condition in which there was a continuous 1 minute
period of compressor operation, with neither
Evaporator water flow nor a" contactor interrupt failure"
diagnostic active. The presence of this software error
message suggests an internal software problem has
been detected. The events that led up to this failure, if
known, should be recorded and transmitted to Trane
Controls Engineering.
Local