EasyManua.ls Logo

Trane Tracer CH530 - Page 49

Trane Tracer CH530
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
49RLC-SVU05A-E4
Diagnostic Name Affects
Ta r g e t
Severity Persistence Active
Modes
[Inactive
Modes]
Criteria Reset
Level
Comm Loss: Oil Return
Gas Pump Fill -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #1
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #1
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Water Pump Relay
Chiller Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Condenser
Water Pump Relay
Chiller Normal Latch All
RTWD only: Continual loss of communication between
the MP and the Functional ID has occurred for a 30
second period.
Remote
Comm Loss: Ice-Making
Status
Chiller Special Action Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Chiller shall revert to normal (non-ice building) mode
regardless of last state.
Remote
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Starter 1A Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Local
Comm Loss: Starter 2A Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Local
Comm Loss: Electronic
Expansion Valve,
Circuit #1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Electronic
Expansion Valve,
Circuit #2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Starter 1A Comm
Loss: MP
Circuit Immediate Latch All
Starter has had a loss of communication with the MP
for a 15 second period.
Local