Diagnostics
49RLC-SVU05A-E4
Diagnostic Name Affects
Ta r g e t
Severity Persistence Active
Modes
[Inactive
Modes]
Criteria Reset
Level
Comm Loss: Oil Return
Gas Pump Fill -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #1
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #1
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #2
Circuit Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Water Pump Relay
Chiller Normal Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Condenser
Water Pump Relay
Chiller Normal Latch All
RTWD only: Continual loss of communication between
the MP and the Functional ID has occurred for a 30
second period.
Remote
Comm Loss: Ice-Making
Status
Chiller Special Action Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Chiller shall revert to normal (non-ice building) mode
regardless of last state.
Remote
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Starter 1A Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Local
Comm Loss: Starter 2A Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Local
Comm Loss: Electronic
Expansion Valve,
Circuit #1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Electronic
Expansion Valve,
Circuit #2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Starter 1A Comm
Loss: MP
Circuit Immediate Latch All
Starter has had a loss of communication with the MP
for a 15 second period.
Local