EasyManua.ls Logo

Trane Tracer CH530 - Communication Loss Diagnostics (cont.)

Trane Tracer CH530
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CG-SVU02C-E450
Diagnostics
Diagnostic Name Affects
Ta r g e t
Severity Persistence Active
Modes
[Inactive
Modes]
Criteria Reset
Level
Starter 2A Comm
Loss: MP
Circuit Immediate Latch All Starter has had a loss of communication with the MP
for a 15 second period.
Local
Comm Loss: Local
BAS Interface
Chiller Info NonLatch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful communication
is established with the LonTalk LLID (LCIC) or BacNet
LLID (BCIC).
Remote
Comm Loss: Op
Status Programmable
Relays
None Info Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Starter
Panel High
Temperature Limit ,
Compressor 1A
None Info Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Local
Comm Loss:
Condenser Rfgt
Pressure Output
Chiller Info Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Cond
Head Press Cntrl
Output
Chiller Immediate Latch All Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Chiller %
RLA Output
Chiller Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Fan
Inverter Fault,
Circuit #1
Circuit
(fan
control)
Special Mode (or in
single fan deck:
Circuit Immediate
shutdown)
Latch (or in
single fan
deck:Latch)
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For
single fan deck configurations, this diagnostic causes a
latching circuit shutdown
Remote
Comm Loss: Fan
Inverter Fault,
Circuit #2
Circuit
(fan
control)
Special Mode (or in
single fan deck:
Circuit Immediate
shutdown)
Latch (or in
single fan
deck:Latch)
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For
single fan deck configurations, this diagnostic causes a
latching circuit shutdown
Remote
Comm Loss: Fan
Inverter Speed
Command,
Circuit #1
Circuit
(fan
control)
Special Mode (or in
single fan deck:
Circuit Immediate
shutdown)
Latch (or in
single fan
deck:Latch)
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For
single fan deck configurations, this diagnostic causes a
latching circuit shutdown
Remote
Comm Loss: Fan
Inverter Speed
Command,
Circuit #2
Circuit
(fan
control)
Special Mode (or in
single fan deck:
Circuit Immediate
shutdown)
Latch (or in
single fan
deck:Latch)
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For
single fan deck configurations, this diagnostic causes a
latching circuit shutdown
Remote
Comm Loss: Fan
Control Relays,
Circuit #1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Fan
Control Relays,
Circuit #2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Ext Noise
Setback Command
None Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Noise
Setback Relay
None Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Evaporator Off-cycle
Freeze Protection
Relay
None Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period.
Remote

Related product manuals