EasyManua.ls Logo

Trane Tracer MP581

Trane Tracer MP581
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Providing low-voltage power for inputs and outputs
CNT-SVN01C-EN 19
Providing low-voltage power for inputs
and outputs
The Tracer MP581 controller can provide low-voltage power to inputs and
outputs. Figure 11 on page 20 shows the location of the low-voltage screw
terminals on the termination board. The following limitations apply:
Four 24 Vdc screw terminals supply a total of up to 250 mA of power.
Two 24 Vac screw terminals supply a total of up to 50 VA of power.
The 50 VA of available power supplies both the 24 Vac screw termi-
nals and binary outputs.
Note that more than one input or output can receive power from a given
screw terminal. The only limitation is the total amount of power supplied.