BAS-SVX62E-EN 11
Overview
Device Connections
The following table provides information about the types of device connections.
Note: In addition, Eight (8) expansion points can be added for XM30 or XM32 expansion modules.
Table 4. Device connections
Connection Quantity Types Range Notes
Analog input
(AI1 to AI3)
3
Temperature 10 kthermistor
AI1 to AI3 can be configured for timed override
capability.
Setpoint 189 to 889
Resistive 100 to 100 k Typically used for fan speed switch.
Universal input
(UI1 and UI2)
2
Linear 0–20 mA
These inputs may be configured to be thermistor or
resistive inputs, 0–10 Vdc inputs, or 0–20 mA inputs.
Linear 0–10 Vdc
Temperature 10 kthermistor
Setpoint 189 to 889
Resistive 100 to 100 k
Binary Open collector/dry contact Low impedance relay contacts recommended.
Pulse Solid state open collector Minimum dwell time is 25 ms On and 25 ms Off.
Binary input (BI1) 1 24 Vac detect
The UC210 controller provides the 24 Vac that is
required to drive the binary inputs when using the
recommended connections.
Binary output (BO1
to BO5)
5 TRIAC (BO2 to BO5)
0.5 A max @24 Vac, resistive and
pilot duty
Used as binary outputs and modulating 3-wire floating
point. TRIAC switches to ground.
Analog output/
binary input
(AO1/BI4 and
AO2/BI5)
2
Linear output
0–20 mA
Each termination must be configured as either an
analog output or binary input.
Linear output 0–10 Vdc
Binary input Dry contact
PWM output 80 Hz signal @ 15 Vdc
Pressure inputs
(PI1)
1 3-wire 0–5 in H
2
O
Pressure inputs supplied with 5 volts of power.
Designed for Kavlico™ pressure transducers.
Overall Point Total 14