EasyManua.ls Logo

Trane Tracer UC210 - Controller Specifications and Dimensions

Trane Tracer UC210
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX62E-EN 7
Overview
Controller Specifications and Dimensions
Ta b l e 1 . Controller storage, operating, and compliance information
Figure 1. Dimensions (with Actuator)
Storage
Temperature: -40°F to 185°F (-40°C to 85°C)
Humidity: 5% to 95% (non-condensing)
Operating
Temperature: -40°F to 158°F (-40°C to 70°C)
Humidity: 5% to 95% (non-condensing)
Power:
20-4–27.6 Vac, (24 Vac ±15% nominal, 50–60 Hz, 10.5 VA plus 1 VA per 20mA of 24 VDC load plus
12 VA maximum per binary load. See Table 6, p. 15 for sizing details.
Environmental Rating (Enclosure): NEMA 1
Installation: U.L. 840: Category 3
Pollution: U.L. 840: Degree 2
Agency Compliance
• UL916 PAZX- Open Energy Management Equipment
• UL94-5V Flammability
•CE Marked
• FCC Part 15, Subpart B, Class B Limit
• AS/NZS CISPR 22:2006
• VCCI V-3/2008.04
• ICES-003, Issue 4:2004
• Communications BACnet MS/TP, supports BACnet protocol ASHRAE 135-2004 and meets BACnet Testing Laboratory (BTL) as an Application Specific Controller (ASC)
profile device
• Suitable for Plenum mounting
U
C
210
251.4 mm
(9.90 in.)
120.0 mm
(4.72 in.)

Table of Contents