BAS-SVX62E-EN 7
Overview
Controller Specifications and Dimensions
Ta b l e 1 . Controller storage, operating, and compliance information
Figure 1. Dimensions (with Actuator)
Storage
Temperature: -40°F to 185°F (-40°C to 85°C)
Humidity: 5% to 95% (non-condensing)
Operating
Temperature: -40°F to 158°F (-40°C to 70°C)
Humidity: 5% to 95% (non-condensing)
Power:
20-4–27.6 Vac, (24 Vac ±15% nominal, 50–60 Hz, 10.5 VA plus 1 VA per 20mA of 24 VDC load plus
12 VA maximum per binary load. See Table 6, p. 15 for sizing details.
Environmental Rating (Enclosure): NEMA 1
Installation: U.L. 840: Category 3
Pollution: U.L. 840: Degree 2
Agency Compliance
UL916 PAZX- Open Energy Management Equipment
UL94-5V Flammability
•CE Marked
FCC Part 15, Subpart B, Class B Limit
AS/NZS CISPR 22:2006
VCCI V-3/2008.04
ICES-003, Issue 4:2004
Communications BACnet MS/TP, supports BACnet protocol ASHRAE 135-2004 and meets BACnet Testing Laboratory (BTL) as an Application Specific Controller (ASC)
profile device
Suitable for Plenum mounting
U
C
210
251.4 mm
(9.90 in.)
120.0 mm
(4.72 in.)

Table of Contents