EasyManua.ls Logo

Trane Tracer UC210 - Controller Specifications and Dimensions

Trane Tracer UC210
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX62E-EN 7
Overview
Controller Specifications and Dimensions
Ta b l e 1 . Controller storage, operating, and compliance information
Figure 1. Dimensions (with Actuator)
Storage
Temperature: -40°F to 185°F (-40°C to 85°C)
Humidity: 5% to 95% (non-condensing)
Operating
Temperature: -40°F to 158°F (-40°C to 70°C)
Humidity: 5% to 95% (non-condensing)
Power:
20-4–27.6 Vac, (24 Vac ±15% nominal, 50–60 Hz, 10.5 VA plus 1 VA per 20mA of 24 VDC load plus
12 VA maximum per binary load. See Table 6, p. 15 for sizing details.
Environmental Rating (Enclosure): NEMA 1
Installation: U.L. 840: Category 3
Pollution: U.L. 840: Degree 2
Agency Compliance
UL916 PAZX- Open Energy Management Equipment
UL94-5V Flammability
•CE Marked
FCC Part 15, Subpart B, Class B Limit
AS/NZS CISPR 22:2006
VCCI V-3/2008.04
ICES-003, Issue 4:2004
Communications BACnet MS/TP, supports BACnet protocol ASHRAE 135-2004 and meets BACnet Testing Laboratory (BTL) as an Application Specific Controller (ASC)
profile device
Suitable for Plenum mounting
U
C
210
251.4 mm
(9.90 in.)
120.0 mm
(4.72 in.)

Table of Contents

Related product manuals