Table 4. Analog Values (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AV320
Compressor 2
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV321
Compressor 2
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only
AV322
Compressor 2
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Read Only
AV323
Compressor 2
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Read Only
AV324
Compressor 2
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Read Only
AV325
Compressor 2 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 2
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV326
Compressor 2 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 2
Compressor with
Cond Reg Valve
Minimum Valve position for the
condenser regulating valve.
Read Only
AV327
Compressor 2 Run
Hours
None
0 -
9999999827968
Units with 2
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
AV328
Compressor 2
Sequence Number
None 0 - 5
Units with 2
Compressor
Sequence Number to indicate what
sequence the compressor will start in.
Read Only
AV333
Compressor 3
Calculated Diff
Refrigerant Pressure
PSI
-500 psi to 500
psi
Units with 3
Compressor
Calculated Differential Pressure
between the Discharge and Suction
Pressure Sensors
Read Only
AV334
Compressor 3
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV335
Compressor 3
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only
AV336
Compressor 3
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Read Only
AV337
Compressor 3
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Read Only
AV338
Compressor 3
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Read Only
AV339
Compressor 3 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 3
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV340
Compressor 3 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 3
Compressor with
Cond Reg Valve
Minimum Valve position for the
condenser regulating valve.
Read Only
AV341
Compressor 3 Run
Hours
None
0 -
9999999827968
Units with 3
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
AV342
Compressor 3
Sequence Number
None 0 - 5
Units with 3
Compressor
Sequence Number to indicate what
sequence the compressor will start in.
Read Only
AV347
Compressor 4
Calculated Diff
Refrigerant Pressure
PSI
-500 psi to 500
psi
Units with 4
Compressor
Calculated Differential Pressure
between the Discharge and Suction
Pressure Sensors
Read Only
AV348
Compressor 4
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 4
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV349
Compressor 4
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 4
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only
AV350
Compressor 4
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 4
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Writeable
AV351
Compressor 4
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 4
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Writeable
AV352
Compressor 4
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 4
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Writeable