BAS-SVP042A-EN
Table 4. Analog Values (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AV353
Compressor 4 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 4
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Writeable
AV354
Compressor 4 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 4
Compressor with
Cond Reg Valve
Minimum Valve position for the
condenser regulating valve.
Writeable
AV355
Compressor 4 Run
Hours
None
0 -
9999999827968
Units with 4
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
AV356
Compressor 4
Sequence Number
None 0 - 5
Units with 4
Compressor
Sequence Number to indicate what
sequence the compressor will start in.
Read Only
AV361
Compressors Available
None -1000 to 1000 All Units
Number of Compressor which are
available to run.
Read Only
AV363
Condenser Control
Percent of Design
Percent 50 % to 100 %
Water Cooled
Condenser Units
Only
sets the percentage of the Control
Pressure Setpoint that will be used to
control the Discharge Pressure on the
unit
Writeable
AV364
Condenser Design
Max Pressure
PSI
-500 psi to 500
psi
Water Cooled
Condenser Units
Only
Condenser Max Design Pressure set by
the Factory.
Read Only
AV365
Condenser Purge Time
(Min)
None 5 to 60
Water Cooled
Condenser Units
Only
Time that the Compressor regulating
valves will be open during purge mode
Writeable
AV366
Condenser Control
Pressure Setpoint
PSI
-500 psi to 500
psi
Water Cooled
Condenser Units
Only
Calculated Condenser Control
Pressure Setpoint based on the
Percentage of Design and the Max
Pressure
Read Only
AV368
Condenser Tee
Strainer Calculated
Diff Press
PSI
-10 psi to 10 psi
Water Cooled
Condenser Units
Only
Calculated Differential Pressure
between the High and Low Condenser
Tee Strainer sensors.
Read Only
AV369
Condenser Tee
Strainer Calculated
High Pressure
PSI
-10 psi to 600 psi
Water Cooled
Condenser Units
Only
Calculated High Pressure based off
High Pressure input and High Pressure
Offset
Read Only
AV370
Condenser Tee
Strainer Calculated
Low Pressure
PSI
-10 psi to 600 psi
Water Cooled
Condenser Units
Only
Calculated Low Pressure based off Low
Pressure input and Low Pressure
Offset
Read Only
AV371
Condenser Tee
Strainer Diff Pressure
Alarm Setpt
PSI
-500 psi to 500
psi
Water Cooled
Condenser Units
Only
Alarm Setpoint to generate alarm for a
dirty strainer Tee based on the
differential pressure.
Writeable
AV372
Condenser Tee
Strainer High Pressure
Offset
PSI
-15 psi to 15 psi
Water Cooled
Condenser Units
Only
Offset applied to the High Pressure
reading to calibrate the sensor with a
local gauge.
Writeable
AV373
Condenser Tee
Strainer Low Pressure
Offset
PSI
-15 psi to 15 psi
Water Cooled
Condenser Units
Only
Offset applied to the Low Pressure
reading to calibrate the sensor with a
local gauge.
Writeable
AV375
Condenser Valve
Control P Gain
None 0.1 to 10 All Units
P Gain for the PID Condenser
Calculation
Read Only
AV378
Duct Static Pressure
Safety Lockout
Setpoint
in(H2O)
-5.0 to 5.0 in
(H2O)
All Units
If the Duct Static exceeds this
Setpoint it will shut down the unit and
require a manual reset.
Writeable
AV380
Variable Speed
Compressor Ramp Up
Delay (Sec)
None 30 to 250
Units with variable
speed compressor
(s)
This delay time disabled the Speed
PID calculation from calculating until
the delay time expires, due to the
automatic ramp up built into the VFD
Read Only
AV382
Water Side Econ
Calculated Enable
Setpoint
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Water
Side Economizer
Temperature that the entering water
must be in order to enable the Water
side economizer for cooling.
Read Only
AV383
Water Side Econ
Sample Time (Min)
None 1 to 5
Units with Water
Side Economizer
time that the Water Side Economizer
will sample the water to see if it can
use for cooling.
Writeable
AV384
Water Side Econ Valve
Control P Gain
None -1000 to 1000
Units with Water
Side Economizer
P Gain for the PID Condenser
Calculation
Read Only
AV385
Water Side
Economizer Enable
Offset
Temperature 4 - 7 Degrees
Units with Water
Side Economizer
This is used to calculate the Water
Side Econ Enable Setpoint
Writeable
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss