BAS-SVP042A-EN
25
Table 7. Binary Values (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV62 Fan Latch None None All Units
Open = Off
Closed = Fan Run
Read Only
BV63
Startup Delay
Completed
None None All Units
Open = No
Closed = Yes
Read Only
BV65 Fan Safeties OK None None All Units
Open = No
Closed = Yes
Read Only
BV72
Diagnostic: Dirty Air
Filter
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Read Only
BV76
Active CoolCoil Control
Sensor Failed
None None All Units
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Read Only
BV190
Compressor 1
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
BV191
Compressor 1 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BV193
Compressor 1 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Writeable
BV194
Compressor 1 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
BV195
Compressor 1 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV196
Compressor 1 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV197
Compressor 1 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
BV200
Compressor 2
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
BV201
Compressor 2 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BV203
Compressor 2 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Writeable
BV204
Compressor 2 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
BV205
Compressor 2 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV206
Compressor 2 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV207
Compressor 2 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
BV210
Compressor 3
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
BV211
Compressor 3 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BV213
Compressor 3 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Writeable
BV214
Compressor 3 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
BV215
Compressor 3 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV216
Compressor 3 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV217
Compressor 3 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
BV220
Compressor 4
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
BV221
Compressor 4 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BV223
Compressor 4 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Writeable
BV224
Compressor 4 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
BV225
Compressor 4 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV226
Compressor 4 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Writeable
BV227
Compressor 4 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
BV250
Compressor Cond
Valve Installed
None None All Units
Open = Not Installed
Closed = Installed
Read Only
BV251
Condenser Water Flow
Type
None None All Units
Open = Variable Flow
Closed = Constant Flow
Writeable
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss