Table 7. Binary Values (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV255
Water Side
Economizer Lockout
BAS
None None
Units with Water
Side Economizer
Open = Available
Closed = Locked Out
Read Only
BV260
Diagnostic:
Compressor 1
Discharge Pressure
Sensor Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV261
Diagnostic:
Compressor 1 Frostat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV262
Diagnostic:
Compressor 1 High
Pressure Shutdown
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV263
Diagnostic:
Compressor 1 High
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV264
Diagnostic:
Compressor 1 Low
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV265
Diagnostic:
Compressor 1 Safety
Circuit Alarm
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV266
Diagnostic:
Compressor 1 Suction
Pressure Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV267
Diagnostic:
Compressor 1 Suction
Temperature Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV270
Diagnostic:
Compressor 2
Discharge Pressure
Sensor Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
Read Only
BV271
Diagnostic:
Compressor 2 Frostat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV272
Diagnostic:
Compressor 2 High
Pressure Shutdown
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV273
Diagnostic:
Compressor 2 High
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV274
Diagnostic:
Compressor 2 Low
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV275
Diagnostic:
Compressor 2 Safety
Circuit Alarm
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV276
Diagnostic:
Compressor 2 Suction
Pressure Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV277
Diagnostic:
Compressor 2 Suction
Temperature Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Read Only
BV280
Diagnostic:
Compressor 3
Discharge Pressure
Sensor Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only