Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV277
Diagnostic:
Compressor 2 Suction
Temperature Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
Writeable
BV280
Diagnostic:
Compressor 3
Discharge Pressure
Sensor Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Writeable
BV281
Diagnostic:
Compressor 3 Frostat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Writeable
BV282
Diagnostic:
Compressor 3 High
Pressure Shutdown
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Writeable
BV283
Diagnostic:
Compressor 3 High
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only
BV284
Diagnostic:
Compressor 3 Low
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only
BV285
Diagnostic:
Compressor 3 Safety
Circuit Alarm
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only
BV286
Diagnostic:
Compressor 3 Suction
Pressure Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only
BV287
Diagnostic:
Compressor 3 Suction
Temperature Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
Read Only
BV290
Diagnostic:
Compressor 4
Discharge Pressure
Sensor Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV291
Diagnostic:
Compressor 4 Frostat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV292
Diagnostic:
Compressor 4 High
Pressure Shutdown
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV293
Diagnostic:
Compressor 4 High
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only