BAS-SVP042A-EN
41
Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV294
Diagnostic:
Compressor 4 Low
Superheat
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV295
Diagnostic:
Compressor 4 Safety
Circuit Alarm
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV296
Diagnostic:
Compressor 4 Suction
Pressure Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Read Only
BV297
Diagnostic:
Compressor 4 Suction
Temperature Sensor
Failure
None None
Units with 1
Compressor
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 4 Failure Reset or Power Cycle.
Writeable
BV322
Diagnostic: Condenser
Water Flow Loss
None None
Water Cooled
Condenser Units
Only
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Writeable
BV72
Diagnostic: Dirty Air
Filter
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Read Only
BV320
Diagnostic: Dirty
Condenser Tee Filter
None None
Water Cooled
Condenser Units
Only
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Read Only
BV19
Diagnostic: Discharge
Air Low Temperature
Lockout
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Alarm Reset or Power Cycle.
Read Only
BV42
Diagnostic: Discharge
Air Temperature
Source Failure
None None All Units
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Read Only
BV15
Diagnostic: Duct
Static Pressure Failure
None None
Units with Duct
Pressure Sensor
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Read Only
BV321
Diagnostic: Software
High Duct Static Alarm
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Filter Alarm Reset or Power Cycle.
Writeable
BV11
Diagnostic: Space
Temperature Source
Failure
None None
Units with Space
Temperature Option.
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Writeable
AV129
Dirty Air Filter DP
Setpoint
Pressure
in(H2O)
-10.0 to 5.0 in
(H2O)
All Units
Filter pressure which will generate a
dirty filter alarm when the filter
differential pressure exceeds it.
Read Only
AV24
Discharge Air Cooling
Setpoint BAS
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
User Entered Setpoint to control the
Discharge Air to when in the cooling
mode.
Read Only
AV18
Discharge Air Cooling
Setpoint Max BAS
Temperature
(°C or °F)
10°C (50°F) to
29.4°C (85°F)
Units with Discharge
Air Reset Method.
Sets the maximum Reset Temperature
when in the cooling mode.
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss