Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
MV3
Heat Cool Mode
Request
None None All Units
[1, Auto]
[2, Heat]
[3, Morning Warm-up]
[4, Cool]
[5, Night Purge]
[6, Pre Cool]
[7, Off]
[8, Test]
[9, Emergency Heat]
[10, Fan Only]
[11, Free Cool]
[12, Ice-Making]
[13, Maximum Heat]
[14, Economizer]
[15, Dehumidify]
[16, Calibrate]
Read Only
MV4 Heat Cool Mode Status None None All Units
[1, Auto]
[2, Heat]
[3, Morning Warm-up]
[4, Cool]
[5, Night Purge]
[6, Pre Cool]
[7, Off]
[8, Test]
[9, Emergency Heat]
[10, Fan Only]
[11, Free Cool]
[12, Ice-Making]
[13, Maximum Heat]
[14, Economizer]
[15, Dehumidify]
[16, Calibrate]
Read Only
BV329
Local Auto Stop
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
MV79
Mechanical Cooling
Stages Failed
None None All Units
[1, 1 Comp Failed]
[2, 2 Comp Failed]
[3, 3 Comp Failed]
[4, 4 Comp Failed]
[5, None Failed]
Read Only
MV80
Mechanical Stages
Active
None None All Units
[1, 0 Compressors]
[2, 1 Compressor]
[3, 2 Compressors]
[4, 3 Compressors]
[5, 4 Compressors]
[6, 1 Compressors]
[7, 2 Compressor]
[8, 3 Compressors]
[9, 4 Compressors]
[10, 0 Compressors]
Read Only
BV52
Mixed Air Low Limit
Active
None None
Units with Water
Side Economizer
Read Only
MV39
MJC MSC Factory
Program Version
None None All Units Version 1.4
Read Only
MV82
MSC Unit Discharge
Air Control Strategy
None None All Units
[1, Fixed DA Setpoint]
[2, Return Air Reset]
[3, Space Temp Reset]
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss