44
BAS-SVP042A-EN
Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
MV83 MSC Unit Status None None All Units
[1, Normal]
[2, Unit Off]
[3, Warning Present]
[4, Alarm Present]
[5, Exterior Stop]
[6, Local Stop]
[7, E-Stop]
[8, BAS Fire]
[9, BAS Shutdown]
Read Only
BI29
Occupancy Input
None None All Units
Normally Open Input
Open = Unoccupied
Closed = Occupied
Read Only
MV1
Occupancy Request
None None All Units
[1, Occupied]
[2, Unoccupied]
[3, Occupied Bypass]
[4, Occupied Standby]
[5, Auto]
Read Only
MV2
Occupancy Status
None None All Units
[1, Occupied]
[2, Unoccupied]
[3, Occupied Bypass]
[4, Occupied Standby]
[5, Auto]
Read Only
AI32
Return Air
Temperature Local
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
Local Return Air Tempreature Sensor Read Only
AV227
Return Temperature
Setpoint BAS
Temperature
(°C or °F)
-7.2°C (45°F) to
35°C (95°F)
Units with Return Air
Reset Method.
Setpoint used in the Reset Calculation
based on return air to set the
Discharge Air Setpoint.
Read Only
AV74
Space Temperature
Active
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Discharge
Air Reset Method.
Setpoint the unit is using to control the
discharge air temperature to.
Read Only
AV73
Space Temperature
BAS
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Discharge
Air Reset Method.
Setpoint the unit is using to control the
discharge air temperature to.
Read Only
AI1
Space Temperature
Local
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Space
Temperature Option.
Local Space Temperature Sensor. Read Only
AV227
Space Temperature
Setpoint BAS
Temperature
(°C or °F)
-7.2°C (45°F) to
35°C (95°F)
Units with Return Air
Reset Method.
Setpoint used in the Reset Calculation
based on return air to set the
Discharge Air Setpoint.
Read Only
BV63
Startup Delay
Completed
None None All Units
Open = No
Closed = Yes
Read Only
BV330
Supply Fan 1
Calculated Status
None None
Units with at least 1
Supply Fan
Open = Off
Closed = On
Read Only
BV331
Supply Fan 1 Failure
None None
Units with at least 1
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV332
Supply Fan 1 Lockout
BAS
None None
Units with at least 1
Supply Fan
Open = Available
Closed = Locked Out
Read Only
AO96
Supply Fan 1 Speed
Command
Percent
0% to 100%
Speed
Units with at least 1
Fan
Analog signal that Controls the Fan
Speed
Read Only
BO100
Supply Fan 1 Start
Stop Command
None None
Units with at least 1
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI80
Supply Fan 1 VFD
Fault
None None
Units with at least 1
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV335
Supply Fan 2
Calculated Status
None None
Units with at least 2
Supply Fan
Open = Off
Closed = On
Read Only
BV336
Supply Fan 2 Failure
None None
Units with at least 2
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV337
Supply Fan 2 Lockout
BAS
None None
Units with at least 2
Supply Fan
Open = Available
Closed = Locked Out
Read Only
AO97
Supply Fan 2 Speed
Command
Percent
0% to 100%
Speed
Units with at least 2
Fan
Analog signal that Controls the Fan
Speed
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss