Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BO101
Supply Fan 2 Start
Stop Command
None None
Units with at least 2
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI81
Supply Fan 2 VFD
Fault
None None
Units with at least 2
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Writeable
BV340
Supply Fan 3
Calculated Status
None None
Units with at least 3
Supply Fan
Open = Off
Closed = On
Writeable
BV341
Supply Fan 3 Failure
None None
Units with at least 3
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Writeable
BV342
Supply Fan 3 Lockout
BAS
None None
Units with at least 3
Supply Fan
Open = Available
Closed = Locked Out
Writeable
AO98
Supply Fan 3 Speed
Command
Percent
0% to 100%
Speed
Units with at least 3
Fan
Analog signal that Controls the Fan
Speed
Read Only
BO102
Supply Fan 3 Start
Stop Command
None None
Units with at least 3
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI82
Supply Fan 3 VFD
Fault
None None
Units with at least 3
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Writeable
BV345
Supply Fan 4
Calculated Status
None None
Units with at least 4
Supply Fan
Open = Off
Closed = On
Read Only
BV346
Supply Fan 4 Failure
None None
Units with at least 4
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV347
Supply Fan 4 Lockout
BAS
None None
Units with at least 4
Supply Fan
Open = Available
Closed = Locked Out
Writeable
AO99
Supply Fan 4 Speed
Command
Percent
0% to 100%
Speed
Units with at least 4
Fan
Analog signal that Controls the Fan
Speed
Read Only
BO103
Supply Fan 4 Start
Stop Command
None None
Units with at least 4
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI83
Supply Fan 4 VFD
Fault
None None
Units with at least 4
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Writeable
BV350
Supply Fan 5
Calculated Status
None None
Units with at least 5
Supply Fan
Open = Off
Closed = On
Read Only
BV351
Supply Fan 5 Failure
None None
Units with at least 5
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV352
Supply Fan 5 Lockout
BAS
None None
Units with at least 5
Supply Fan
Open = Available
Closed = Locked Out
Writeable
AO100
Supply Fan 5 Speed
Command
Percent
0% to 100%
Speed
Units with at least 5
Fan
Analog signal that Controls the Fan
Speed
Read Only
BO104
Supply Fan 5 Start
Stop Command
None None
Units with at least 5
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI84
Supply Fan 5 VFD
Fault
None None
Units with at least 5
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Writeable
BV355
Supply Fan 6
Calculated Status
None None
Units with at least 6
Supply Fan
Open = Off
Closed = On
Read Only
BV356
Supply Fan 6 Failure
None None
Units with at least 6
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV357
Supply Fan 6 Lockout
BAS
None None
Units with at least 6
Supply Fan
Open = Available
Closed = Locked Out
Writeable
AO101
Supply Fan 6 Speed
Command
Percent
0% to 100%
Speed
Units with at least 6
Fan
Analog signal that Controls the Fan
Speed
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss