46
BAS-SVP042A-EN
Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BO105
Supply Fan 6 Start
Stop Command
None None
Units with at least 6
Fan
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BI85
Supply Fan 6 VFD
Fault
None None
Units with at least 6
Fan
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV360
Supply Fan Calculated
Status
None None All Units
Open = Off
Closed = Running
Read Only
BV2
Supply Fan Failure
Reset
None None All units
Open = Normal
Closed = Reset
Read Only
AV203
Supply Fan Maximum
Speed Local
Percent 50 % to 150 % All Units
The maximum speed the fan can run
when enabled
Read Only
AV204
Supply Fan Minimum
Speed Local
Percent 15 % to 150 % All Units
The minimum speed the fan can run
when enabled
Read Only
AV101
Supply Fan Speed
Pgain
None 1 to 25 All Units
P Gain for the PID Supply Fan Speed
Calculation
Read Only
AV115
Supply Fan Speed
Status
Percent -150 % to 150 % All Units
Speed the Fans are actually running Read Only
MV90
Supply Fans Failed
None None All Units
[1, 1 Fan Failed]
[2, 2 Fans Failed]
[3, 3 Fans Failed]
[4, 4 Fans Failed]
[5, 5 Fans Failed]
[6, 6 Fans Failed]
[7, None Failed]
Read Only
BO126
Unit Alarm Output
Command
None None All Units
Normally Open Contacts Used Only
Open = No Alarms Closed = Alarm
Present
Normally Closed Contacts not used
Read Only
MV100 Unit Information None None All Units State 1
Read Only
AV380
Variable Speed
Compressor Ramp Up
Delay (Sec)
None 30 to 250
Units with variable
speed compressor
(s)
This delay time disabled the Speed
PID calculation from calculating until
the delay time expires, due to the
automatic ramp up built into the VFD
Read Only
BV365
Warning: Compressor
1 Cond Limit Status
None None
Units with at least 1
Compressor
Open = Normal Capacity
Closed = Limited Capacity
Read Only
BV366
Warning: Compressor
1 Frostat Limit Status
None None
Units with at least 1
Compressor
Open = Normal
Closed = Warning Active
Writeable
BV370
Warning: Compressor
2 Frostat Warning
None None
Units with at least 2
Compressor
Open = Normal
Closed = Warning Active
Read Only
BV371
Warning: Compressor
2 High Discharge
Press Warning
None None
Units with at least 2
Compressor
Open = Normal
Closed = Warning Active
Writeable
BV375
Warning: Compressor
3 Frostat Warning
None None
Units with at least 3
Compressor
Open = Normal
Closed = Warning Active
Read Only
BV376
Warning: Compressor
3 High Discharge
Press Warning
None None
Units with at least 3
Compressor
Open = Normal
Closed = Warning Active
Read Only
BV380
Warning: Compressor
4 Frostat Warning
None None
Units with at least 4
Compressor
Open = Normal
Closed = Warning Active
Read Only
BV381
Warning: Compressor
4 High Discharge
Press Warning
None None
Units with at least 4
Compressor
Open = Normal
Closed = Warning Active
Read Only
AV382
Water Side Econ
Calculated Enable
Setpoint
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Water
Side Economizer
Temperature that the entering water
must be in order to enable the Water
side economizer for cooling.
Read Only
AV383
Water Side Econ
Sample Time (Min)
None 1 to 5
Units with Water
Side Economizer
time that the Water Side Economizer
will sample the water to see if it can
use for cooling.
Read Only
AV384
Water Side Econ Valve
Control P Gain
None -1000 to 1000
Units with Water
Side Economizer
P Gain for the PID Condenser
Calculation
Writeable
AV385
Water Side
Economizer Enable
Offset
▲ Temperature 4 - 7 Degrees
Units with Water
Side Economizer
This is used to calculate the Water
Side Econ Enable Setpoint
Read Only
BV255
Water Side
Economizer Lockout
BAS
None None
Units with Water
Side Economizer
Open = Available
Closed = Locked Out
Read Only