EasyManua.ls Logo

Trane Wired Temperature Sensors - Page 31

Trane Wired Temperature Sensors
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX10C-EN 31
Maintenance and Troubleshooting
Table 1. Resistance measurements for zone temperature and setpoints
Zone or setpoint temperature
Nominal zone temperature
output resistance
Nominal setpoint and heating
setpoint output resistance
** NA 938 Ω
55°F (12.8°C) 17.47 kΩ 792 Ω
60°F (15.6°C) 15.3 kΩ 695 Ω
65°F (18.3°C) 13.5 kΩ 597 Ω
70°F (21.1°C) 11.9 kΩ 500 Ω
75°F (23.9°C) 10.5 kΩ 403 Ω
80°F (26.7°C 9.3 kΩ 305 Ω
85°F (29.4°C) 8.25 kΩ 208 Ω
* NA 49 Ω
Notes:
1. Sensors are calibrated at 70°F (21.1ºC).
2. Single setpoint systems: Varies ±28
Ω at 70°F (21.1ºC); varies ±128 Ω at endpoints of scale 55ºF (12.8ºC) and 85ºF
(29.4ºC). Dual setpoint systems: Cooling setpoint varies ±10
Ω at 70ºF (21.1ºC); varies at ±110 Ω at endpoints of
scale. Heating setpoint varies ±20
Ω at 70ºF (21.1ºC); varies at ±120 Ω at endpoints of scale.
Table 2. Resistance measurements for fan and system modes
Fan mode System mode Nominal output resistance
Auto or invalid Emergency heat 35,000 Ω
Auto or invalid Heat 19,480 Ω
Auto or invalid Auto 7680 Ω
Auto or invalid Off 2320 Ω
Auto or invalid Cool 4870 Ω
On Emergency heat 43,450 Ω
On Heat 27,930 Ω
On Auto 16,130 Ω
On Off 10,770 Ω
On Cool 13,320 Ω
High Invalid (fan control only) 16,130 Ω
Med Invalid (fan control only) 13,320 Ω
Low Invalid (fan control only) 10,770 Ω
Auto Invalid (fan control only) 2320 Ω
Off Invalid (fan control only) 4870 Ω

Table of Contents

Related product manuals