BAS-SVU10C-EN 17
The User Menu Sequence
Override
Resume
Temperature
setpoints
System mode
setting
Fan mode setting
Override
schd Y/N
Temperat
set Y/N
Sys mode
set Y/N
Fan mode
set Y/N
Appears only in
unoccupied mode
Cancel
ovrd Y/N
Appears only in
override mode
There is a default profile set in the thermostat from the factory. This enables the thermostat to
operate as a non-programmable unit in day mode operation at start up.
Programmed default temperature
setpoints:
Programmed default modes:
Occupied cooling setpoint = 75°F (24°C) System mode = Auto
Occupied heating setpoint = 72°F (22°C)
Fan mode = Smart (for models with a
communication mod
ule or programmable stand-
alone models)
Fan mode = Auto (for non-programmable stand-
alone mo
dels)
Unoccupied cooling setpoint = 82°F (28°C)
Unoccupied heating setpoint = 65°F (18°C)
Fahrenheit scale
Setpoint type = Permanent
Detailed Description of Menu Settings
Override an
unoccupied period
This menu will appear only when the thermostat is in unoccupied mode. The
unoccupied mode is enabled either by the internal timer scheduling or by a
remote NSB contact via DI1 or DI2.
Override schd Y/N
If DI1 or DI2 is configured to operate as a remote temporary override
contact, thi
s menu will be disabled.
Answering yes to this prompt will cause the thermostat to go into occupied
mode for an amount of
time equal to the parameter “TOccTime” (1 to 12
hours).
Resume regular
scheduling
This menu does not appear in regular operation. It will appear only when the
thermostat is in Unoccupied override mode.
Cancel Ovrd Y/N
Answering “Yes” to this question will cause the thermostat to resume the
regular p
rogrammed setpoints scheduling.
Permanent
setpoint changes
This menu permits the adjustment of all permanent temperature setpoints
(occupied and unoccupied) as well as the desired temperature units (°F or
°C). Permanent setpoints are written to RAM and EEPROM.
Temperat set Y/N