28 BAS-SVU10C-EN
Specifications
Thermostat power requirements:
19-30 Vac 50 or 60 Hz; 2 VA (RC and C) Class 2 RC to RH
jumper 2.0 Amps 48 VA maximum
Ope
rating conditions:
32°F to 122°F (0°C to 50°C)
0% to 95% R.H. non-condensing
Storage conditions:
-22°F to 122°F (-30°C to 50°C)
0% to 95% R.H. non-condensing
Sensor: Local 10 K NTC thermistor
Resolution: ± 0.2°F (± 0.1°C)
Control accuracy: ± 0.9°F (± 0.5° C) @ 70°F (21°C) typical calibrated
Occupied and unoccupied setpoint range
c
ooling:
54 to 100°F (12.0 to 37.5°C
)
Occupied and unoccupied setpoint range
heating:
40°F to 90°F (4.5°C to 32°C)
Room and outdoor air temperature range -40°F to 122°F (-40°C to 50°C)
Proportional band for room temperature
c
ontrol:
Fact
ory set, heating and cooling at: 2.0°F (1.1°C)
Digital inputs: Relay dry contact only across C terminal to DI1 or DI2
Contact output rating:
Each relay output: (Y1, Y2, G, W1, W2 and AU)
30 Vac, 1 Amp. maximum
30 Vac, 3 Amp. in-rush
Wire gauge 18 gauge maximum, 22 gauge recommended
Dimensions: 4.94 in. x 3.38 in. x 1.13 in.
Approximate shipping weight: 0.75 lb (0.34 kg)
Agency Approval all models:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734
with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (C
anada)
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
CE: EMC Directiv
e 89/336/EEC (European Union)
C-Tick: AS/NZ
S CISPR 22 Compliant (Australia / New
Zealand) Supplier Code Number N10696