BAS-SVU10C-EN 7
Product Overview
Fan lock: Used in conjunction with a local air flow sensor connected to the input. Locks out
the thermostat heating and cooling action and displays a local alarm if no air flow is detected
10 seconds after the fan (G terminal) is energized.
Programmable smart fan operation saves energy during night mode
Non volatile EEPROM memory prevents loss of param
eters during power shortage
Built in default profile set-up for easier start
up and commissioning
Configurable SPST output relay on programmable models fo
r lighting, exhaust fan or fresh air
control
Heat Pump Model Specific Features
The Trane Communicating Thermostat includes the following features:
Selectable single or dual stage compressor stages
H
igh balance point:
Locks out auxiliary heating when outside air
temperature is above this value
Low balance point:
Locks out heat pump compressor operation w
hen
outside air temperature is below this value
Comfort/economy mode:
In economy mode, heat pump use i
s m
aximized before turning on auxiliary heating
Compressor/auxiliary interlock:
Adds flexibility by locking out heat pump operation during auxiliary heating to prevent high
pressure trip when the coil is downstr
eam of the
auxiliary heat source