22 BAS-SVU10C-EN
Installer Configuration Parameter Menu
Anticycle
Minimum on/off
operation time for
stages
Default value = 2
minutes
Anti-short cycling can
be
se
t to 0 minutes for
equipment that posses
their own anti cycling
timer. Do not use that
value unless the
equipment is equipped
with such internal timer.
Failure to do so can
damage the equipment.
Minimum On/Off operation time of cooling and heating stages.
Important: An
ti-sho
rt cycling can be set to 0 minutes for equipment that posses their own anti
cycling timer. Do
not use this value unless the equipment is equipped with such
internal timer. Failure to do so can damage the equipment.
0, 1, 2, 3, 4 and 5 minutes
Heat cph
Heating stages cycles
per
hour
Default value = 4 C.P.H.
For multi
stage models,
heat cph applies to W1
and W2
For heat pump models,
h
eat c
ph applies to W1
only (Emergency heat)
Will set the maximum number of heating stage cycles per hour under normal control operation. It
re
prese
nts the maximum number of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing
mechanic
al components faster.
3, 4, 5, 6, 7 and 8 C.P.H.
cool cph
Cooling stages cycles
per
hour
Default value = 4 C.P.H.
For multi stage models,
cool cph
applies to Y1
and Y2
For heat pump models,
cool cph
applies to Y1
and Y2 in cooling and
heating independently
of the reversing valve
position
Will set the maximum number of cooling stage cycles per hour under normal control operation. It
re
prese
nts the maximum number of cycles that the equipment will turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing
mechanic
al components faster.
3 or 4 C.P.H.
Deadband
Minimum deadband
Defaul
t value = 2.0°F
(1.1°C)
Minimum deadband value between the heating and cooling setp
oints. If modified, it will be applied only
when any of the setpoints are modified.
2, 3 or 4°F (1.0 to 2.0°C)
fan cont
Fan control
Default value = On
For multi stage models,
f
an c
ontrol applies to
W1 and W2
For heat pump models,
f
an c
ontrol applies to
W1 only (Emergency
heat)
Fan control in heating mode.
When selecting On; the thermostat in all cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating
stages (
terminals W1 and W2) are solicited,
will not be energized. The fan in this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan always on.
On or Off
fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds after the call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will le
ave the fan always on.
Off or On
ToccTime
Temporary occupancy
time
Default value = 3 hours
Temporary occupancy time with occupied mode setpoints when override function is enabled When the
thermo
stat is in unoccupied mode, function is enabled with either the menu or DI1 or DI2 configured
as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 and 12 hours
cal RS
Ro
om air temperature
sensor calibration
Default value = 0.0°F or
°C
Offset that can be added/subtracted to actual displayed room temperature
± 5.0°F (± 2.5°C)
Configuration
parameters
Significance
Default value
Adjustments