EasyManuals Logo

TRIATEK UVM-1000 User Manual

TRIATEK UVM-1000
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
UVM-1000
LIT-12013155
30
Figure 12. Dynamic Values Tab
Values displayed include calculated values such as cfm, position,
pressure, etc., and also raw A/D values from the AI inputs. The
values do not automatically update, they need to have their
associated Get XX button clicked to force a value to be read.
The SetPoint entry displays the current converted setpoint for
the actuator as a (times 10) percentage value. If the input, as
dened under the User Settings Tab is set to cfm (not Pos) Input
= checked, then the incoming voltage is interpreted as a cfm and
parsed through the valve curve as a cfm to position.
The resulting percentage (times 10) position is displayed in
the SetPoint eld when the Get Setpoint button is pushed.
Depending on the state of the cfm (not Pos) Input check box, a
cfm or position value can be entered into the Setpoint eld, and
passed to the controller when the Set Setpoint button is pushed.
The passed value will only have e󰀨ect if the Use AI Setpoint on
the User Settings Tab is un-checked. If it is checked, the UVM
will use the voltage on the IN input as the cfm/Position setpoint.
This eld can be used for operational fault nding without having
to have a variable voltage source.
Dynamic Values Tab

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TRIATEK UVM-1000 and is the answer not in the manual?

TRIATEK UVM-1000 Specifications

General IconGeneral
BrandTRIATEK
ModelUVM-1000
CategoryControl Unit
LanguageEnglish