Commissioning
Connecting the device to an EtherNet/IP scanner using RSLogix
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com
07.00 | 2022/09 | 74
Activating QuickConnect via the Class Instance Attribute
Activate QuickConnect via Class Instance Attribute as follows:
Class Instance Attribute Value
0xF5 0x01 0x0C 0: Deactivated (default)
1: Activated
Activating QuickConnect via the web server
Click Parameter Ò Activate QuickConnect Ò Yes.
Fig.64: Setting QuickConnect in the web server