CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 16 May 2006 37
While installing batteries, follow all safety precautions outlined in the appropriate
battery product manuals.
The terminal block for the GMT fuse panel is rated for 20A with factory wiring, but
only 10A for field installation.
All ac inputs for the J85470S1 L12 and L13 must be connected to maximum 60A panel
board breakers from maximum two ac conduit connections.
CPS6000 outputs are not connected to earth. Earthing of rectifier outputs may be
performed externally to the shelf at a “ground window” or “mesh ground”. Connection
of Ringer tip outputs to CPS6000 Battery or Ground is optional via Ringer Chassis
jumper or external connection.
The QS841 has an IEEE 802.3 compliant 10Base-T network interface with a
grounded connector shield.. Where intra building lightning surge protection is of
concern, Tyco Electronics recommends the use of a shielded cable, where both ends
are tied to ground. This cable must be supplied by the user. (example: CAT 5 E STP)