21
Programming Descriptions
Periodic Test Transmission with Trouble - the panel can be programmed to transmit a Periodic Test Transmission with Trouble Reporting Code in place
of the standard Periodic Test Transmission if any of the following conditions exist.
• Fire Zone Trouble (Zones 1-64)
• Battery Trouble (PC1616/PC1832/PC1864, PC520X)
• Fire Zone Alarm (Zones 1-64, Two-Wire Smoke
• Aux Trouble (PC1616/PC1832/PC1864)
• Fire Trouble (Two-Wire Smoke)
• Bell Trouble (PC1616/PC1832/PC1864)
• Fire Tamper/Low Sensitivity (WLS/AML Zones 1-32)
• Module Supervisory
• Fire Zones Bypassed (Zones 1-64)
• Ground Fault (PC5700)
• Fire Supervisory (Wireless/AML Zones 1-32)
• TLM Trouble (PC1616/PC1832/PC1864, PC5700 Line 1-2)
• AC Trouble (PC1616/PC1832/PC1864, PC520X)
• FTC Trouble
Section [350] Communicator Format
Program the 2-digit number for the desired Communicator Format for the First Phone Number and Second Phone Number. When dialing the Third Phone
Number, the system will use the Communicator Format programmed for Phone Number 1. Valid entries are [01] to [13]. Refer to the Programming Work-
sheet for a list of the available Communicator Formats. Refer to Appendix D for Communicator Format details.
Section [351] to [376] Communicator Call Direction Options
Reporting events are categorized into 5 groups; Alarm/Restore, Opening/Closing, Tamper Alarm/Restore, System Maintenance and Test Transmissions.
Program which Phone Number the control panel will use to transmit reporting events by turning the option ON in the correct Section. Phone Number 1
and/or Phone Number 2 can be used.
Section [377] Communicator Variables
Program a 3-digit number for each program entry:
Section [378] Test Transmission Time
Program the time the system will report a Test Transmission reporting event. Program 4 digits – [HH][MM] using military standard.
For a test transmission at 11:00 pm, program data [23][00]). Valid entries are [00][00] to [23][59].
Section [379] Periodic DLS Time of Day
Programs the time the system will auto-call DLS. Program 4 digits – [HH][MM] using military standard. For a DLS auto-call at 11:00 pm, program data
[23][00]). Valid entries are [00][00] to [23][59]. Programming [99][99] will select a random time, [FF][FF] will disable it.
Section [380] First Communicator Option Code
Swinger Shutdown (Alarms): Maximum number of alarm/restoral transmissions per zone. Valid entries: [001] to [014]. Program data [000] to
disable shutdown.
Swinger Shutdown (Tamper): Maximum number of tamper alarm/restoral transmissions per zone. Valid entries: [000] to [014]. Program data [000]
to disable shutdown.
Swinger Shutdown (Trouble): Maximum number of trouble alarm/restoral transmissions per trouble condition. Valid entries: [000] to [014].
Program data [000] to disable shutdown.
Communicator (Transmission) Delay: Time, in seconds, panel will delay reporting an alarm event. Valid entries: [000] to [255].
AC Failure Communication Delay: Time, in minutes, panel will delay reporting an AC trouble event. Valid entries: [000] to [255].
TLM Trouble Delay: Time, in 3 second checks, before the system will consider the phone line disconnected. Valid entries: [002] to [255]
(e.g., 3 x10 seconds = 30 seconds). NOTE: TLM Restoral follows the same delay.
Test Transmission Cycle (Land Line): Number of days between test transmission reporting events. Valid entries: [001] to [255].
For Future Use
Wireless Zone Low Battery Delay: Number of days the system will delay reporting a wireless low battery to the central station.
Valid entries: [000] to [255]. Program data [000] for no delay.
Delinquency Transmission Delay: Number of hours (Activity Delinquency) or days (Arming Delinquency) the panel will delay before transmitting
the event to the central station. Valid entries: [001] to [255].
Communication Cancel Window: Time, in minutes, after an alarm has occurred that the system will report a Communication Cancel reporting event
if the system is disarmed. They keypad will beep rapidly to indicate the Communication Cancel reporting event has been communicated successfully.
Valid entries: [001] to [255].
Option
Description
[1] ON: the system communicator is enabled. OFF: the communicator is disabled.
[2] ON: the system transmits alarm restorals if the zone is restored and the bell has timed out.
OFF: the system transmits alarm restorals immediately when the zone is restored.
[3] ON: the panel uses rotary (pulse) dialing. OFF: the panel uses touchtone (DTMF) dialing