22
PowerSeries - PC1616/PC1808/PC1832/PC1864
Section [381] Second Communicator Option Code
Section [382] Third Communicator Option Code
Section [389] TL/GS Fault Check Timer
Program the period of time (in seconds) in between checks to see if the TL/GS module is present. Valid entries are [001]-[255].
Section [401] First Downloading Option Code
[4] ON: the panel will switch from touchtone dialing to rotary dialing after the 4th failed attempt to communicate.
OFF: the panel will use DTMF dialing for all dialing attempts.
[5] ON: the system uses the Third Phone Number to back up the First Phone Number. OFF: the Third Phone Number is disabled.
[6] ON: the system alternates between the First Phone Number and Third Phone Number when attempting to report an event.
OFF: the panel will dial the First Phone Number for the programmed number of attempts, then switch to the Third Phone Number.
[7] For future Use
[8] ON: the Delinquency feature follows zone activity. OFF: the Delinquency feature follows arming.
Option
Description
[1] ON: the keypad beeps 8 times after successfully transmitting the Opening After Alarm reporting event.
OFF: the keypad does not beep.
[2] ON: the bell output squawks 8 times after successfully transmitting the Opening After Alarm reporting event.
OFF: the bell output does not activate.
[3] ON: the system uses programmed reporting codes when transmitting using the SIA format.
OFF: the system automatically generates all reporting codes transmitted.
[4] ON: the system beeps the keypad 8 times after successfully transmitting a Closing reporting event.
OFF: the keypad does not beep.
[5] ON: the system requests a Listen in/Two-way session the next time it calls the 1st/3rd Phone Number when the PC59xx transmits a request.
OFF: the system ignores the request from the PC59xx.
This Option is used with PC59xx series modules.
[6] ON: the system requests a Listen in/Two-way session the next time it calls the 2nd Phone Number when the PC59xx transmits a request.
OFF: the system will ignore the request from the PC59xx.
This Option is used with PC59xx series modules.
[7] ON: the system uses Contact ID format programmed reporting codes when transmitting reporting codes.
OFF: the system automatically generates all reporting codes transmitted.
[8] For Future Use
Option
Description
[1] ON: the system will use the digit [5] as the first digit of the Partial Closing reporting code when transmitting Contact ID reporting codes.
OFF: the system will use the digit [4] as the first digit of the Partial Closing reporting code when transmitting Contact ID reporting codes.
[2] ON: the system will transmit all alarms during Walk Test.
OFF: the system will not report alarm events during Walk Test.
[3] ON: the keypad will display the message ‘Communications Cancelled’ (programmable LCD) or ‘CC’ (fixed-message LCD) upon
successful transmission of the Communication Cancelled reporting event.
OFF: the keypad will not display these messages.
[4] ON: the system dials the Call Waiting Cancel String on the first attempt to dial the central station.
OFF: the system does not dial the Call Waiting Cancel String.
[5] ON: enables support for the TL/GS module. OFF: disables TL/GS.
[6] ON: the AC Failure Transmission Delay Timer will use hours. OFF: the delay will be in minutes.
[7] ON: Sets the number of Dialing attempts to 1 when using Residential Dial Format.
OFF: Residential Dial follows Dialing Attempt Counter.
[8] For Future Use
Option
Description
[1] ON: the system answers incoming calls for downloading (either Programmed Number of Rings or Double Call). OFF: the system does not
answer incoming calls using the double call routine for downloading.
These settings do not affect the 6 hour DLS downloading window on power up.
[2] ON: the user can enable downloading for the DLS Window using the [][6] command. OFF: the user cannot enable downloading.