Adapting the unit to the heating installation
40 ecoTEC plus installation and maintenance instructions 0020134823_01
12
Code Parameters Adjustable values
Factory
setting
Your own
setting
D.000 Heating partial load Adjustable heating partial load in kW
auto: Unit automatically adjusts max. partial load to
current system demand)
Auto
D.001 Overrun time of internal heating pump for
heating mode
2–60min 5min
D.002 Max. burner anti-cycling time heating at
20 °C flow temperature
2–60min 20min
D.017 Heating flow/return regulation changeover 0 = Flow, 1 = Return 0 do not
adjust
D.018 Pump operating mode setting 1 = Comfort (continuously operating pump)
3 = Eco (intermittently operating pump)
3 = Eco
D.027 Switching of relay 1 on the
"2 in 7" multi-functional module VR 40
1 = Circulation pump
2 = Ext. pump
3 = Charging pump
4 = Extractor hood
5 = Ext. solenoid valve
6 = Ext. error message
7 = Not active
8 = Remote control eBUS (not yet supported)
9 = Anti-legionella pump (not active)
1
D.028 Switching of relay 2 on the
"2 in 7" multi-functional module VR 40
1 = Circulation pump
2 = Ext. pump
3 = Charging pump
4 = Extractor hood
5 = Ext. solenoid valve
6 = Ext. error message
7 = Not active
8 = Remote control eBUS (not yet supported)
9 = Anti-legionella pump (not active)
2
D.046 Pump type 0 = Relay with disable facility
1 = PWM with disable facility
0
D.050 Offset for minimum speed In rpm, adjustment range: 0 to 3000 Rated value
D.051 Offset for maximum speed In rpm, adjustment range: -990 to 0 Rated value
D.071 Target value maximum heating flow tem-
perature
40 to 85 °C 75 °C
D.072 Internal pump overrun after cylinder
charging
Adjustable from 0 to 10min 2min
D.077 Partial load for cylinder charging [kW]
D.084 Maintenance indicator: Number of hours
until the next maintenance
Adjustment range: 0 to 3010hrs und "-" for deacti-
vated
"-"
D.093 DSN unit variant setting Adjustment range: 0 to 99
D.094 Delete fault history 1 = Delete fault list
D.096 Factory setting 1 = Reset all adjustable parameters to factory setting
12.1 Adjustable parameters of the diagnostics menu