EasyManuals Logo

Vaillant ECOTEC PLUS VU 80 User Manual

Vaillant ECOTEC PLUS VU 80
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Inspection and maintenance
46 ecoTEC plus installation and maintenance instructions 0020134823_01
13
13.1.3 Checking the CO
2
content
The CO
2
content must be checked/set in the following
cases:
When replacing the gas valve
If you suspect incorrect combustion.
At initial start-up
During any maintenance work
When replacing the fan or burner
If there are changes to the gas installation
1
13.1 Checking the CO
2
content
i
The boiler is equipped with a flue gas analysis
point (1). A suitable flue gas measuring instru-
ment can be used to check the combustion per-
formance of the measuring instrument at this
analysis point.
> Remove the front casing (¬section4.6).
> Start check programme P.1 (¬section11.4).
> Wait at least 5 minutes until the boiler reaches its
operating temperature.
> If required, remove the upper casing.
> Measure the CO
2
content at the flue gas analysis point
(1). Compare the measured value with the corresponding
value in ¬table13.1.
Settings Unit
Natural gas H
Tolerance
CO
2
after 5 minutes full load
operation with front casing
closed
Vol.-% 9.0 +/- 0.5
CO
2
after 5 minutes full load
operation with front casing
removed
Vol.-% 8.8 +/- 0.5
Set for Wobbe Index W
0
kWh/m
3
15
13.1 Gas default settings
> If all these points meet the requirements, continue in
accordance with ¬section 13.2.
> If one of the flue gas values is above the permissible
value in ¬table13.1, continue in accordance with the
following ¬section 13.1.4.
13.1.4 Setting the CO
2
content (or setting the air
ratio)
a
Danger!
Increased risk of poisoning from incor-
rect setting.
If one of the flue gas values is above the
permissible values in ¬table 13.1:
> Check that the entire flue gas system is
in good condition.
> Check that the seals of the combustion
system are in good condition.
> Check the gas connection pressure (gas
flow pressure).
> Check the gas volume flow.
1
1
806/5-5
1006/5-5
1206/5-5
13.2 Carry out the CO
2
measurement, air index setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ECOTEC PLUS VU 80 and is the answer not in the manual?

Vaillant ECOTEC PLUS VU 80 Specifications

General IconGeneral
BrandVaillant
ModelECOTEC PLUS VU 80
CategoryBoiler
LanguageEnglish

Related product manuals