Inspection and maintenance
54 ecoTEC plus installation and maintenance instructions 0020134823_01
13
8
9
10
11
13
5
6
7
12
11
8
10
12
5
6
7
9
13
806/5-5
1006/5-5
1206/5-5
4
4
13.12 Installing the gas-air mixture unit
> Connect the gas-air mixture unit (5) to the heat
exchanger (7).
> Tighten the screws (6) in a cross-wise pattern until the
burner door fits closely and uniformly onto the mating
surfaces. Tightening torque: 10 Nm
> Connect the plugs of the ignition lines and the ground
connection to the ignition electrode (9) on the ignition
transformer.
> Connect the plug of the ionisation line to the ionisation
electrode (11) and connect the plug of the ground con-
nection to the earthing lug.
> Connect the plug of the safety cut-out to the upper
safety cut-out (8).
> Connect the plugs (12 and 13) to the fan motor.
> Connect the plug (10) to the gas valve.
> Connect the gas pipe (4) with a new seal to the gas
valve.
Torque (for the VU GB 806/5-5 only): 2Nm
Torque (for the VU GB 1006/5-5 and VU GB 1206/5-5
only): 2.8Nm
> Open the gas isolator cock on the boiler.
a
Danger!
Risk of poisoning and fire caused by
escaping gas!
Gas can escape through leaks.
> Check the gas tightness at the gas con-
nection using leak detection spray.
For the VUGB806/5-5 only: Installing the air intake pipe
2
1
13.13 Installing the air intake pipe (Only for VUGB806/5-5)
> Check that the sealing ring in the air intake pipe (2) is
positioned correctly in the seal seat.
> Place the air intake pipe back onto the intake nozzle.
> Secure the air intake pipe with the clip (1) on the intake
nozzle.
For all units:
> Close the electronics box.
> Re-establish the connection to the power mains.
> Open the service valves in the heating flow and in the
heating return.
> If required, refill the boiler with water to a pressure of
between the minimum and the maximum values.
13.5.7 Checking the gas connection pressure
(gasflow pressure)
> Check the gas connection pressure (¬section9.6.3).
13.5.8 Checking the CO
2
content
> Check the CO
2
content (section 13.1.3).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ECOTEC PLUS VU 80 and is the answer not in the manual?

Vaillant ECOTEC PLUS VU 80 Specifications

General IconGeneral
BrandVaillant
ModelECOTEC PLUS VU 80
CategoryBoiler
LanguageEnglish

Related product manuals