ecoTEC plus installation and maintenance instructions 0020134823_01 9
a
Safety
a
2
b
Caution.
Risk of material damage if the heating
water is treated with unsuitable frost or
corrosion protection agents!
Frost and corrosion protection agents may
cause changes in the seals, noises during
heating and may lead to further damage.
> Do not use any unsuitable frost or corro-
sion protection agents.
Mixing additives with the heating water may result in mate-
rial damage. However, no incompatibility with Vaillant boil-
ers has been detected with proper use of the following
products over a long period.
> When using additives, follow the manufacturer's instruc-
tions without exception.
Vaillant accepts no liability for the compatibility of any addi-
tive or its effectiveness in the rest of the heating installa-
tion.
Additives for cleaning measures (subsequent
flushing required)
Fernox F3
Sentinel X 300
Sentinel X 400
Additives intended to remain permanently in the
system
Fernox F1
Fernox F2
Sentinel X 100
Sentinel X 200
Additives for frost protection intended to remain
permanently in the system
Fernox Antifreeze Alphi 11
Sentinel X 500
> Inform the operator about the measures required if you
have used these additives.
> Inform the operator about the measures required for
frost protection.
Permissible salt content
Heating water
characteristics
Unit Low-salt Saline
Electrical conductivity at
25 °C
mS/cm < 100
100 - 1500
Appearance
Free of sedimentary
materials
pH value at 25 °C 8.2 - 10.0
1)
8.2 - 10.0
1)
Oxygen mg/l
< 0.1 < 0.02
1) For aluminium and aluminium alloys, the pH value range is
restricted from 6.5 to 8.5.
2.2 Guideline values for heating water: Salt content
Permissible water hardness
b
Caution.
Heating water that is extremely calcifer-
ous or corrosive or contaminated by
chemicals may cause damage to the
boiler.
Unsuitable heating water damages the
seals and diaphragms, blocks components
in the boiler and heating installation
through which the water flows, and causes
noise.
The heating water must fulfil the limit val-
ues based on the system volume in accord-
ance with fig.2.1 and, if required, must be
treated.
In addition, the national regulations with
regard to water treatment shall apply.
To treat the water, we recommend treat-
ment plants that work according to the
reverse osmosis process.
> Condition the water for the initial filling
as well as the water for any subsequent
fillings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ECOTEC PLUS VU 80 and is the answer not in the manual?

Vaillant ECOTEC PLUS VU 80 Specifications

General IconGeneral
BrandVaillant
ModelECOTEC PLUS VU 80
CategoryBoiler
LanguageEnglish

Related product manuals